Circular No. 30/2019/TT-BCT dated November 18, 2019 of the Ministry of Industry and Trade on amending and supplementing a number of articles of the Circular No. 25/2016/TT-BCT dated November 30, 2016 of the Ministry of Industry and Trade on regulations on electricity transmission system and the Circular No. 39/2015/TT-BCT dated November 18, 2015 of the Minister of Industry and Trade on regulations on electricity distribution system

  • Summary
  • Content
  • Status
  • Vietnamese
  • Download
Save

Please log in to use this function

Send link to email

Please log in to use this function

Error message
Font size:

ATTRIBUTE

Circular No. 30/2019/TT-BCT dated November 18, 2019 of the Ministry of Industry and Trade on amending and supplementing a number of articles of the Circular No. 25/2016/TT-BCT dated November 30, 2016 of the Ministry of Industry and Trade on regulations on electricity transmission system and the Circular No. 39/2015/TT-BCT dated November 18, 2015 of the Minister of Industry and Trade on regulations on electricity distribution system
Issuing body: Ministry of Industry and TradeEffective date:
Known

Please log in to a subscriber account to use this function.

Don’t have an account? Register here

Official number:30/2019/TT-BCTSigner:Tran Tuan Anh
Type:CircularExpiry date:Updating
Issuing date:18/11/2019Effect status:
Known

Please log in to a subscriber account to use this function.

Don’t have an account? Register here

Fields:Electricity , Industry

SUMMARY

Negative sequence voltage components may exceed 3%

On November 18, 2019, the Ministry of Industry and Trade promulgates the Circular No. 30/2019/TT-BCT amending and supplementing a number of articles of Circular No. 25/2016/TT-BCT dated November 30, 2016 of the Ministry of Industry and Trade on regulations on electricity transmission system and Circular No. 39/2015/TT-BCT dated November 18, 2015 of the Minister of Industry and Trade on regulations on electricity distribution system.

Different from the previous regulations in Circular 25/2016/TT-BCT that: negative sequence voltage components are not allowed to exceed 3% of nominal voltage in case of nominal voltage levels on transmission grid, this Circular regulates that: In some circumstances,  the negative sequence voltage components on the transmission grid at some points of time are allowed to exceed 3% but 95% of the values which is calculated within at least 01 week long with samples taken frequency of every 10 minutes shall not exceed the prescribed limit.

In addition this Circular also:  annuls the regulation on operating and installing low-frequency relays in the System of automatic frequency load shedding; supplements the regulation on definition of rated capacity of a power plant, DIM (Dispatch Instruction Management) - the information management system of dispatch instruction between the dispatching level...

This Decision takes effect on January 03, 2020.

For more details, click here.
Download files here.
LuatVietnam.vn is the SOLE distributor of English translations of Official Gazette published by the Vietnam News Agency
Effect status: Known

THE MINISTRY OF
INDUSTRY AND TRADE

-------------

No. 30/2019/TT-BCT

THE SOCIALIST REPUBLIC OF VIETNAM            

Independence - Freedom – Happiness
------------------

Hanoi, November 18, 2019

CIRCULAR
Amending and supplementing a number of articles of the Circular No. 25/2016/TT-BCT dated November 30, 2016 of the Ministry of Industry and Trade on regulations on electricity transmission system and Circular No. 39/2015/TT-BCT dated November 18, 2015 of the Minister of Industry and Trade on regulations on electricity distribution system

---------------

Pursuant to the Law on Electricity dated December 3, 2004 and the Law dated November 20, 2012 amending and supplementing a number of articles of the Law Electricity;

Pursuant to the Government's Decree No. 98/2017/ND-CP dated August 18, 2017 defining the functions, tasks, powers and organizational structure of the Ministry of Industry and Trade;

Pursuant to the Government's Decree No. 137/2013/ND-CP dated October 21, 2013 detailing the implementation of a number of articles of the Law on Electricity and the Law amending and supplementing a number of articles of the Law on Electricity;

At the request of the Director of Electricity Regulatory Authority;

The Minister of Industry and Trade promulgates the Circular amending and supplementing a number of articles of Circular No. 25/2016/TT-BCT dated November 30, 2016 of the Ministry of Industry and Trade on regulations on electricity transmission system and Circular No. 39/2015/TT-BCT dated November 18, 2015 of the Minister of Industry and Trade on regulations on electricity distribution system

Article 1. Amending and supplementing a number of articles of Circular No. 25/2016/TT-BCT dated November 30, 2016 of the Ministry of Industry and Trade on regulations on electricity transmission system

1. Adding Clause 5a following Clause 5, Clause 6a following Clause 6 of Article 3 as follows:

“5a. Rated capacity of a power plant is the total rated capacity of the generating sets in such power plant in stable and normal operation mode and declared by the manufacturer in the design description of the generating sets. For solar power plants, the rated capacity of a solar power plant is the maximum alternating electric power of such plant that can be calculated and announced in line with the planned DC capacity of such solar power plant.

6a. DIM (Dispatch Instruction Management) is the information management system of dispatch instruction between the dispatching level with control authority and the power plant or the Control Center of power plants.”

2. Amending Clauses 10, 35, 49 and 53 of Article 3 as follows:

“10. Frequency adjustment in an electricity system (hereinafter referred to as frequency adjustment) is an adjustment process in an electricity system to maintain the stable operation of such system, including primary frequency adjustment, secondary frequency adjustment, and tertiary frequency adjustment:

a) Primary frequency adjustment is the process of adjusting electricity system frequency immediately by a large number of generating sets equipped with a governor.

b) Secondary frequency adjustment is the adjustment process following the primary frequency adjustment carried out through the impact of AGC system to keep the frequency within the permissible long-term working band.

c) Tertiary frequency adjustment is the adjustment process following the secondary frequency adjustment carried out by a dispatch instruction to keep the electricity system frequency operating stably according to current regulations and ensure economical distribution of generating capacity among generating sets.

35. Short-term flicker perceptibility (Pst) and long-term flicker perceptibility (Plt) are values calculated according to current National Standards. In case the Pst and Plt values ​​are not included in the National Standards, they shall be calculated according to the current IEC Standards published by the International Electrotechnical Commission.

49. PSS (Power System Stabilizer) is a device that injects additional signals into the automatic voltage regulator (AVR) to decrease voltage fluctuation in the electricity system.

53. Automatic load shedding is the act of automatically cutting loads by relays in accordance with the signals of frequency, voltage or transmission power of the electricity system when such frequency, voltage or transmission power level drops below the permissible limits calculated by the electricity system and market operator.”.

3. Amending Article 7 as follows:

“Article 7. Phase balance

Click Download to see the full text

Please log in to a subscriber account to see the full text. Don’t have an account? Register here
Please log in to a subscriber account to see the full text. Don’t have an account? Register here
Processing, please wait...
LuatVietnam.vn is the SOLE distributor of English translations of Official Gazette published by the Vietnam News Agency

ENGLISH DOCUMENTS

LuatVietnam's translation
Circular 30/2019/TT-BCT PDF

This utility is available to subscribers only. Please log in to a subscriber account to download. Don’t have an account? Register here

* Note: To view documents downloaded from LuatVietnam.vn, please install DOC, DOCX and PDF file readers
For further support, please call 19006192

SAME CATEGORY

Circular No. 24/2019/TT-BCT dated November 14, 2019 of the Ministry of Industry and Trade on amending and supplementing a number of articles of the Circular No. 45/2018/TT-BCT dated November 15, 2018 of the Minister of Industry and Trade, prescribing the operation of competitive wholesale electricity market, and amending and supplementing a number of articles of the Circular No. 56/2014/TT-BCT dated December 19, 2014 of the Minister of Industry and Trade, prescribing methods of determination of electricity generation costs and processes for inspecting power purchase agreement

Circular No. 24/2019/TT-BCT dated November 14, 2019 of the Ministry of Industry and Trade on amending and supplementing a number of articles of the Circular No. 45/2018/TT-BCT dated November 15, 2018 of the Minister of Industry and Trade, prescribing the operation of competitive wholesale electricity market, and amending and supplementing a number of articles of the Circular No. 56/2014/TT-BCT dated December 19, 2014 of the Minister of Industry and Trade, prescribing methods of determination of electricity generation costs and processes for inspecting power purchase agreement

Commerce - Advertising , Electricity , Industry

loading